建国220kV变电站#3主变油中溶解气体色谱分析数据报表
主变名称220k建国3#变型号SSZ11-180000/220出厂日期2017.12
出厂序号201708042额定容量(kVA)180000/180000/90000/54000kVA联结组别YNyn0ynO+d11
负载损耗(kW)中压-低压142.29高压-中压650.08高压-低压172.66空载损耗(kW)94.58空载电流(%)0.164%
额定电流(A)短路阻抗(%)高中13.56中低 7.98高低 23.32
额定电压(kV)(220±8*1.25%)/121/38.5/10.5kV制造厂正泰电气股份有限公司
浓度单位:μL/L
取样日期H2COCO2CH4C2H6C2H4C2H2总烃上层油温(℃)取样部位初步分析意见负荷(MW)
2024.10.1226.98293.63692.873.160.380.3503.8920.07下部正常2.1
2024.03.203.9562.45590.651.580001.5811.39下部正常7.68
2024.1.422291.92640.22.110002.1111.7下部正常6.43
2023.10.2624.35258.83578.32.560.30.2903.1530.6下部正常2.5
2023.7.2123.03257.06647.012.420002.4240.6下部正常4.76
2023.4.2622.34268.24540.992.180002.1826下部正常11.05
2023.2.1522.5241.4606.72.10002.125.9下部正常14.6
2022.12.1623.7245.6529.32.100.602.712下部正常4.69
2022.9.1422.6236.4592.8200.302.335.3下部正常10.7
2022.5.2023221.6511.72000234.9下部正常7.57
2022.2.1524.1223.8453.4200.302.311.5下部正常5.2
2021.12.1722.1214.2553.22.10002.111.7下部正常2.28
2021.7.2320.6170.7555.11.60.20.101.952下部正常9.4
2021.5.2922178.6449.41.800.502.439下部正常5.22
2021.1.2121.2167.4518.81.90.60.302.916下部正常2.8
2020.10.2316.5142.7399.41.40001.417下部正常2.3
2020.8.1216.9127.5495.61.40001.435下部正常12.7
2020.4.816.6118.6352.11.20001.236下部正常3.1
2020.1.1514.394.5314.30.90000.93下部正常2.6
2019.10.1613.6105420.31.20001.232下部正常6
2019.7.310.378.1346.50.80000.844下部正常1.7
2019.4.186.752.32611.40.8002.326下部正常7.3
2019.1.33.331.7394.80.60000.623下部正常(投运第三十天)6.3
2018.11.122.928.5212.60.50000.532下部正常(投运第十天)54
2018.11.52.831.2190.30.50000.528下部正常(投运第四天)
2018.11.22.930220.80.50000.529下部正常(投运第一天)12
2018.10.92.227.4219.50.50000.5下部正常(投运前)12